Cable Analyzer Home   Cable Testers and Harness Testers Made Easy!

 

                Cable Testing Products        Support        Information Center        About Us        Contact Us

 

Insulation Compression Failures
in Cables

 


Quick View Logo
compress-350-e (19K)

Compression damage can cause insulation to fail, causing current leakage, arcing, and even dead shorts.






compress-350-c (27K)

This close up shows how even plastic tie wraps can cause compression damage on soft insulation.







crushwire-a-350 (29K)

Metal brackets, grommets, clamps, overly tight strain relief's, all can cause cable failures due to compression damage.







compress-350-1 (26K)

Bare wire, tightly wrapped around braided shielding and then soldered, caused DWV failures in this cable.





Test Results:

Failures indicated while testing the cable
  • Shorts both intermittent and constant
  • Failed Hipot - DWV and "Over Current"

Necessary Conditions:

Pressure on insulation in a bundle of wires from anything like the following
  • Cable Ties
  • Clamps
  • Routing of wires through holes in sheet metal where the holes do not have soft grommets.
  • Tight fitting strain relief's
  • Wrapping bare wire around exposed shielding to make a soldered connection.
  • Insulated wires on the factory floor that get stepped on with hard soled shoes, run over with wheeled carts, etc. during the assembly process.

Aggravating Conditions:

Conditions that could contribute to, or worsen, the effects of this problem
  • Heat from soldering shields.
  • Unusually soft wire insulation such as is found in highly flexible cables or coax cable with "foam" insulation
  • Sharp edges on components brought in contact with wire insulation.
  • Thin-wall wire insulation

Root Cause:

Insulation that has narrowed from its normal thickness due to compression from physical features/components in the assembly or in the environment of the installed application.

Understanding the Failure Mechanism:

  • Insulation on a wire has "plastic characteristics" that under pressure will cold flow and reduce the insulation wall thickness. If there is another wire, a metal connector shell, or other metal components close by, the insulation between wires or between a wire and another metal component will likely breakdown with hipot testing. Hipot testing is a good method to predict shorts that may appear later (a latent defect). The more "soft" the insulation, the higher the susceptibility to this type of failure.

  • If heat is applied to components under compression like when adding heat shrink coverings or soldering to shields, the problem often occurs in PVC insulations too and even in very "hard" insulations such as TFE.

Confirmation of Root Cause:

One or more of the following might be used to verify the defect
  1. A solid short usually can be isolated with a VOM or low voltage continuity tester. Sometimes this requires cutting the failed wire at a point before and after the compression to prove that the failure occurs at the compression point.
  2. If the wire insulation cannot be easily inspected for problems or none are visible you can,   a.) divide and conquer or,    b.) make the problem more solid.
  • A.  Divide and Conquer: Perform a destructive test by cutting a cable in two and separating the cut wires. Perform a shorts and/or a hipot test on each separate side of the cable. (on Cirris testers you can do a "no connects" shorts/hipot test.) Be sure to use, "apply HV to all pins" with "Single Net Failure" set to "Fails Hipot" or "High Cap Shield" set to NO. Continue this process discovering which end had the problem and at what point the problem is detected or eliminated.
  • B.  Make the problem more solid: Heat (bake) the cable, (don't exceed the acceptable storage temperature of the cable) to increase the rate of cold flow. A heat gun is less controlled but could also be used. After the application of heat, the problem should be more consistent. Another way to surface this problem is to apply salt water in the area of a compression, (if it is not near any uninsulated areas such as connector contacts). The wire insulation should be impermeable to salt water. Wires that are insulated, including the shield which may not be insulated, should still read off-scale for resistance with a VOM. If the resistance drops then begin the divide and conquer approach with resistance measurements.

    After confirming the point of failure you may want to inspect the damage under a microscope by removing the wire(s) from the bundle in the compression area.

General Recommendations:

  1. If you are using wire with a soft insulation, do not rely on wire insulation in any compression zone. If the compression cannot be eliminated or appropriately reduced, insulated tubing over the wire might add to the normal insulation.

  2. If you are using heat near wire insulation where wires are bundled together, carefully evaluate the application to avoid insulation damage.
Case Studies
   

Problem 1

A cable assembly house experienced a jump in DWV failures in their cables. The cable contained a number of TFE insulated and shielded twisted pair wires. The shields were terminated as a group by exposing about .3" of the shield and wrapping a bare wire around the exposed shields and then soldering them. Previously these cables had been built with a separate shield termination for each wire.


Discovery

Using the confirmation methods, they discovered that the wrapped bare wire was creating compression and the soldering was allowing the TFE insulation of the twisted pairs to short to the shields.

Solution

Assemblers returned to using shield terminations that were designed to heat shrink and solder terminate.
   

Problem 2

Another cable assembly house was building cables used in GPS systems in motor homes. A large percentage of the cables failed hipot testing but, since no visually apparent problem was found, and the customer didn't require hipot testing, it was dropped. In time assemblies were returned as defective. Testing with low voltage, most of these defectives still passed as good.


Discovery

When testing on a high voltage tester, the returned cables failed consistently with DVW failures. Using the "divide and conquer" method the problem was traced to pieces of braided shielding that were penetrating extremely soft insulation on wires that were tightly fastened with a cable tie.

Solution

Extra insulation was added to the areas where the insulation breach compression failures were occurring.
   

Cirris Systems - Cable Testing Tips - Compression Errors
Toll-free 1-800-441-9910